Model
|
SUN-18K-G04
|
SUN-20K-G04
|
SUN-25K-G04
|
|
Input Side
|
||||
Max. DC Input Power(kW)
|
21.6
|
26
|
32.5
|
|
Max. DC Input Voltage (V)
|
1000
|
|||
Start-up DC Input Voltage(V)
|
250
|
|||
MPPT Operating Range(V)
|
200~850
|
|||
Max. DC Input Current(A)
|
32+32
|
|||
Max. Short Circuit Current (A)
|
48+48
|
|||
Number of MPPT/Strings per MPPT
|
2/ 2
|
2 / 2
|
2 / 3
|
|
Output Side
|
||||
Rated Output Power(kW)
|
18
|
20
|
25
|
|
Max. Active Power(kW)
|
19.8
|
22
|
27.5
|
|
Rated AC Grid Voltage(V)
|
220 / 380, 230 / 400
|
|||
AC Grid Voltage Range(V)
|
277Vac~460Vac(this may vary with grid standards)
|
|||
Rated Grid Frequency(Hz)
|
50 / 60 (Optional)
|
|||
Operating Phase
|
Three phase
|
|||
Rated AC Grid Output Current(A)
|
26.1
|
29
|
36.2
|
|
Max. AC Output Current(A)
|
28.7
|
31.9
|
39.9
|
|
Output Power Factor
|
0.8 leading to 0.8 lagging
|
|||
Grid Current THD
|
<3%
|
|||
DC Injection Current(mA)
|
<0.5%
|
|||
Grid Frequency Range
|
47~52 or 57~62 (Optional)
|
|||
Efficiency
|
||||
Max.Efficiency
|
98.6%
|
|||
Euro Efficiency
|
97.8%
|
|||
MPPT Efficiency
|
>99%
|
|||
Protection
|
||||
DC Reverse-Polarity Protection
|
Yes
|
|||
AC Short Circuit Protection
|
Yes
|
|||
AC Output Overcurrent Protection
|
Yes
|
|||
Output Overvoltage Protection
|
Yes
|
|||
Insulation Resistance Protection
|
Yes
|
|||
Ground Fault Monitoring
|
Yes
|
|||
Islanding Protection
|
Yes
|
|||
Temperature Protection
|
Yes
|
|||
Integrated DC Switch
|
Yes
|
|||
Remote software upload
|
Yes
|
|||
Remote change of operating parameters
|
Yes
|
|||
Surge protection
|
DC Type II / AC Type II
|
|||
General Data
|
||||
Size(mm)
|
330W×508H×206D
|
|||
Weight(kg)
|
20.8
|
|||
Topology
|
Transformerless
|
|||
Internal Consumption
|
<1W (Night)
|
|||
Running Temperature
|
-25~65ºC
|
|||
Ingress Protection
|
IP65
|
|||
Noise Emission(Typical)
|
<45dB
|
|||
Cooling Concept
|
Smart cooling
|
|||
Max. Operating Altitude Without Derating
|
2000m
|
|||
Designed Lifetime
|
>20 years
|
|||
Grid Connection Standard
|
EN50549-1,VDE 0126-1-1
|
|||
Operating Surroundings Humidity
|
0-100%
|
|||
Safety EMC/Standard
|
IEC62109-1/-2,IEC61000-6-2,IEC61000-6-4
|
|||
Features
|
||||
DC Connection
|
MC-4 mateable
|
|||
AC Connection
|
IP65 rated plug
|
|||
Display
|
LCD 1602
|
|||
Interface
|
RS485/RS232/Wifi/LAN
|
|||